STATUS INSTRUMENTS / RAIL MOUNT TEMPERATURE TRANSMITTERS

SEM1605PV

DIN RAIL WITH RTD (Pt100) I/P AND VOLTAGE O/P

  • ACCEPTS PT100, Cu100, Cu53, Ni100, Ni120 SENSORS
  • 3 WIRE 0 to 10 V OUTPUT
  • USER OUTPUT TRIM (ZERO and SPAN)
  • PC CONFIGURATION USING USB PORT

ราคาและระยะเวลานำเข้าขึ้นกับรุ่นและจำนวน ทีมงานตอบกลับภายใน 1 วันทำการ

01 / OVERVIEW

ภาพรวม

The SEM1605PV is a DIN rail mounted Voltage Output temperature transmitter from Status Instruments. It has been designed to accept common RTD temperature sensor inputs and provide the user with a standard three wire (0 to 10) volt output signal. The output signal is linear to temperature.

Designed for ease of use, our latest USB interface is fitted for quick and easy configuration. Just connect a standard USB cable between the SEM1605PV and your PC. Our free configuration software will guide you through any changes you wish to make. To further help save time, the SEM1605PV does not need to be wired to a power supply during the configuration process, it is powered via the USB interface from your PC.

02 / FEATURES

คุณสมบัติเด่น

Active Range

The SEM1605PV is provided with a user push-button ranging option, allowing adjustments at both 0 V and 10 V against a live input. The ‘user adjust’ function can be locked during configuration if not required. The state LED indicates out of range input during normal operation; during ‘user adjust’ it is also used to indicate the stage of adjustment.

(0 and 10) V Trim

The buttons can also be used for 0 V and 10 V trim adjustment to add small offsets to (0 or 10) V output.

Sensor Referencing

The SEM1605PV sensor referencing, via the Windows based USB-Speedlink software, allows for close matching to a known reference sensor, eliminating possible sensor errors.

Sensor Burn Out Detection

If a sensor wire is broken or becomes disconnected, the SEM1605PV output will automatically go to its user-defined level (upscale or downscale) or a pre-set value.

Stability

The SEM1605PV DIN rail transmitter incorporates digital technology to ensure accurate low-drift performance.

USB PC Configuration

The SEM1605PV is quick and easy to configure using a standard-type USB lead and the free-of-charge USB-SpeedLink Windows software.

USB Android View

The SEM1605PV can be connected to an android phone or tablet using an OTG USB adaptor. Running a free App, the Android device can then be used to view live data from SEM1605PV.